Title 124 - NEBRASKA DEPARTMENT OF ENVIRONMENTAL QUALITY

Chapter 8 - SEPTIC TANK DESIGN

All septic tanks regardless of material or method of construction shall conform to the following criteria as shown in Figures 8.1, 8.2, 8.3, and 8.4.

001 The depth from the invert of the outlet to the floor of the tank (liquid depth) of any septic tank or compartment thereof shall not be less than 42 inches and a liquid depth greater than 78 inches shall not be considered in determining tank capacity. The diameter of a septic tank shall not be less than 60 inches and the length shall be approximately two to three times the width.

002 No tank or compartment thereof shall have an inside horizontal dimension less than 24 inches.

003 Inlet and outlet connections of the tank shall be provided with baffles. See Figure 8.5.

004 The space in the tank between the liquid surface and the top of the inlet and outlet baffles shall be not less than 20 percent of the total required liquid capacity, except that in horizontal cylindrical tanks this space shall be not less than 15 percent of the total required liquid capacity.

005 Inlet and outlet baffles shall be constructed of acid resistant concrete, acid resistant fiberglass, or plastic.

006 Sanitary tees shall be affixed to the inlet or outlet pipes with a permanent waterproof adhesive. Baffles shall be integrally cast with the tank, affixed with a permanent waterproof adhesive, or affixed with stainless steel connectors top and bottom.

007 The inlet baffle shall extend at least 6 inches but not more than 20 percent of the total liquid depth below the liquid surface and at least one inch above the crown of the inlet sewer.

008 The outlet baffle and the baffles between compartments shall extend below the liquid surface a distance equal to 40 percent of the liquid depth except that the penetration of the indicated baffles or sanitary tees for horizontal cylindrical tanks shall be 35 percent of the total liquid depth. They also shall extend above the liquid surface as required in item 004. In no case shall they extend less than six inches above the liquid surface.

009 There shall be at least 1 inch between the underside of the top of the tank and the highest point of the inlet and outlet devices.

010 The inlet invert shall be not less than 2 inches above the outlet invert.

011 The inlet and outlet shall be located opposite each other along the axis of maximum dimension and shall be constructed of noncorrosive materials. The horizontal distance between the nearest points of the inlet and outlet devices shall be at least 4 feet.

012 Sanitary tees shall be at least 4 inches in diameter. Inlet baffles shall be located no less than 6 inches or no more than 12 inches measured from the end of the inlet pipe to the nearest point on the baffle. Outlet baffles shall be located 6 inches measured from beginning of the outlet pipe to the nearest point on the baffle.

013 Access to the septic tank shall be as follows:

014 Compartmentation of single tanks.

015 Multiple Tanks

Figure 8.1 Septic Tank, Profile View

Figure 8.1
Figure 8.2
Figure 8.3
Figure 8.4
Figure 8.5
T124Ch8Figures.pdf
File Size 89 KB


Enabling Legislation: Neb. Rev. Stat. §81-1505(8).
Legal Citation: Title 124, Ch. 8, Nebraska Department of Environmental Quality


Nebraska Department of Environmental Quality
1200 "N" Street, Suite 400
P.O. Box 98922
Lincoln, Nebraska 68509
(402) 471-2186